Avoid circuit overloading and related outages
Thursday, March 18th, 2010Dynamic day-to-day operations sometimes require that data center operators deploy additional equipment without taking time to validate the overall capacity available from circuit breakers. Although adequate processes may be in place, overloaded breakers always seem to fail at the worst possible instant -for example, when an outage affects main power circuits, moving all loads onto backup circuits.
New energy monitoring tools such as Arch Rock Energy Optimizer let users set thresholds on electrical circuits to generate an alert, typically before the power supply has exceeded its “nameplate” rating and well before the actual capacity of a breaker is reached. Different thresholds can be selected depending on the organization’s “safety tolerance.” Figure 1 shows examples of possible thresholds set on the “Apparent Power” metric:
- A 63-amp circuit on 400 volts monitored for 50%, 80% or 100% load
- 12.6 kVA is equivalent to 50% load
- 20.2 kVA is equivalent to 80% load
- 25.2 kVA is equivalent to 100% load
- A 32-amp circuit on 230V monitored for 50%, 80% or 100% load
- 3.68kVA is equivalent to 50% load
- 5.88kVA is equivalent to 80% load
- 7.36kVA is equivalent to 100% load
Figure 1 - Setting a threshold on the Apparent Power metric (e.g. 32-amp circuit at 80% load)

















Subscribe to RSS